Three-Phase Pad-Mounted Transformer

Three phase pad mounted transformers are designedand manufactured in compliance with all applicableANSI and DOE2016 standards. All transformers are oil-filledD65Crise,and designed for usual serviceconditions per IEEE C57.12.00.Ratings available are 30 through 3000 kVA withprimary voltages 2.4 through35 kV (150 kV BIL) andsecondary voltages up to 600 volts. All standard tapconfigurations available:dual voltage in mostcombinations, dual voltage with taps only (seriesconnection only) and impedance and loss optionsavailable in most designs.

  • Fully Custom
  • Expedited Production Processing

Dimensions

Three-Phase Pad-Mounted Transformer Specs Image
Technical SpecificationTechnical Specification          
Capacity(KVA) HV Tapping range LV No-load loss load loss impedance efficiency
75 2400 4160 7200 7620 12000 12470 13200 13800 14400 19920 24940 34500             ±2 x2.5%   110 120 208 240 277 347 415 416 480 600 690 130 100             4.0-6.3 99.03
152 200 1800 99.16
225 350 3100 99.23
300 430 3700 99.27
500 600 5410 99.35
750 880 7500 99.4
1000 1000 10300 99.43
1500 1400 14500 99.48
2000 1800 18300 99.51
2500 2300 23100 99.53
3150
3750
recommend

Our Recent Products