S13 Three-Dimensional Wound Core

The S13 three-dimensional wound core transformeris an oil-immersed transformer adopting a three-phase three-dimensional wound core structure. As atype of energy-saving power transmission andtransformation equipment, it is mainly used in thetechnical renovation projects of urban and ruralpower grids. Its core is fabricated by continuously winding high-quality cold-rolled silicon steel strips andundergoing vacuum annealing. The surface is coatedwith epoxy resin paint for moisture protection andcuring. This transformer boasts such technicaladvantages as low no-load loss, low no-load currentand low operating noise.

  • Fully Custom
  • Expedited Production Processing

Product Features

Low Losses

In accordance with the current national standard GB/T 6451-2015 Technical Parameters and Requirements for Three-phase Oil-immersed Power Transformers, forthe capacity range of 30-1600 kVA, the no-load loss of the S13-M.RL series is reducedby an average of 50% and the load loss by an average of 30%; the no-load loss of theS11-M.RL series is reduced by an average of 30% and the load loss by an average of 25%.



Low No-load Current

Benefiting from the premium material of the wound core and the advantages of itswinding process, the no-load current is significantly reduced. In line with the nationalstandard GB/T 6451-1999, the no-load current of both the S13-M.RL series and S11-M.RLseries is reduced by an average of 75%.


Low Operating Noise

Complying with the noise standard JB/T 10088-1999, the noise level of both the S13-M.RL and S11-M.RL series is lowered by approximately 7-9 dB.


Strong Short-circuit Withstand Capability

The transformer core assembly is integrally structured as a three-dimensional triangular prism. Stay bolts are installed around the assembly and in the central area,forming an integral structure with the upper & lower yoke insulations and laminatedwooden blocks. This design can effectively resist the axial and radial mechanical stresses generated during sudden short-circuit faults.

Dimensions

Technical Parameter  
Rated capacity(KVA) Voltage combination (KVA) Vector group No-load loss load loss Short-circuit impedance No-load current
50   Y,yno 95 810           4 0.6
63   Y,yno 110 990 0.6
80   Y,yno 130 1160 0.5
100 6±5 % Y,yno 150 1400 0.5
125 6.3±5 % Y,yno 170 1710 0.5
160 10±5 % Y,yno 200 2100 0.4
200 11±5 % Y,yno 245 2460 0.4
250 0.4 Y,yno 300 2800 0.4
315   Y,yno 340 3400 0.3
400   Y,yno 420 4100 0.3
500   Y,yno 490 4850 0.3