35 kV S(B)HX-M Series Amorphous Alloy Oil-Immersed Transformer

This product features an oil-filled, hermetically sealed structure with the same operating principle as hermetically sealed power transformers. The amorphous alloy core is composed of elements such as iron, nickel, cobalt, silicon, boron, and carbon. As an isotropic soft magnetic material, it offers low magnetizing power and no structural defects hindering domain wall movement. With an ultra-thin thickness of just 0.027 mm, its stacking factor is correspondingly low at 0.75–0.8. The material also provides extremely high electrical resistivity (3 to 6 times that of silicon steel sheets) and five times the hardness of silicon steel sheets, though it is particularly sensitive to mechanical stress.

  • Fully Custom
  • Expedited Production Processing

Product model

S    B)    H     15    -  M       □    /    □

                              

 

Three-phase                                                            Hermetically sealed

 

LV foil winding (Low-voltage foil winding)             Rated capacity (kVA)

 

Amorphous alloy core                                            Voltage class (kV)

 

Performance level code

 

Dimensions

Technical Parameter    
Rated capacity (KVA) Connect Group Voltage Combination (KVA) No-load loss(W) Load loss(W) No-load current(%) Short-circuit impedance (%)
High voltage (HV) Tapping range Low voltage (LV)
630       Yd11     35     ±5%     3.15 6.3 10.5 830 7870 1.10   6.5
800 980 9410 1.00
1000 1150 11540 1.00
1250 1410 13940 0.90
1600 1700 16670 0.80
2000 2180 18380 0.70
2500 2560 19670 0.60
3150   35-38.5   ±5%   3.15 6.3 10.5 3040 23090 0.56 7.0
4000 3620 27360 0.56
5000 4320 31380 0.48
6300 5250 35060 0.48 7.5
8000     Ynd11     35-38.5   ±5% Or ±2 x 2 .5% 3.15 3.3 6.3 6.6 10.5 11 7200 98500 0.42
10000 8700 45300 0.42
12500 10080 53900 0.40     8.0
16000 12160 95800 0.40
20000 14400 79500 0.40
25000 17020 94100 0.32
31500 20220 112900 0.32
      Note 1: For transformers with a rated capacity of 6300 KVA and below, products with a high-voltage tapping range of ±2×2.5% are available. Note 2: For transformers with low voltages of 10.5 KV and 11 KV, products with a Dyn11 connection group are available. Note 3: For transformers with a rated capacity of 3150 kVA and above, the -5% tap position is the tap with the highest current.
recommend