35KV SZ(11-22) SERIES OIL-IMMERSED

This product series features an advanced design, with significant improvements in materials, structure, and manufacturing processes. It offers strong short-circuit withstand capability, elegant appearance, reliable operation, low losses, and low noise, reaching a level comparable to advanced foreign products of the same type. The prototype of our SZ9-20000/35 transformer successfully passed the sudden short-circuit test conducted by the National Transformer Testing Center on the first attempt. The longitudinal oil channels provided in the high- and low-voltage coils facilitate heat dissipation, significantly reducing the copper-oil temperature difference and the hot-spot temperature rise inside the coils.

  • Fully Custom
  • Expedited Production Processing

Product Model

S      ¨        ¨       ¨       ¨     /  35

                        

 

Three-phase

"F" stands for air-cooled Self-cooling has no code.

Off-circuit (no-excitation) voltage regulation has no code.

 

"Z" stands for on-load voltage regulation.

Loss series

Rated capacity (kVA)

Voltage level (kV) 

Dimensions

Technical Parameter  
Rated capacity (KVA) Connect Group Voltage Combination (KVA) No-load loss(W) Load loss(W) No-load current(%) Short-circuit impedance (%)
High voltage (HV) Tapping range Low voltage (LV)
630       Yd11     35     ±5%     3.15 6.3 10.5 830 7870 1.10   6.5
800 980 9410 1.00
1000 1150 11540 1.00
1250 1410 13940 0.90
1600 1700 16670 0.80
2000 2180 18380 0.70
2500 2560 19670 0.60
3150   35-38.5   ±5%   3.15 6.3 10.5 3040 23090 0.56 7.0
4000 3620 27360 0.56
5000 4320 31380 0.48
6300 5250 35060 0.48 7.5
8000     Ynd11     35-38.5   ±5% Or ±2 x 2 .5% 3.15 3.3 6.3 6.6 10.5 11 7200 98500 0.42
10000 8700 45300 0.42
12500 10080 53900 0.40     8.0
16000 12160 95800 0.40
20000 14400 79500 0.40
25000 17020 94100 0.32
31500 20220 112900 0.32
Note 1: For transformers with a rated capacity of 6300 kVA and below, products with a high-voltage tapping range of ±2×2.5% are available. Note 2: For transformers with low voltages of 10.5 kV and 11 kV, products with a Dyn11 connection group are available.   Note 3: For transformers with a rated capacity of 3150 kVA and above, the -5% tap position is the tap with the highest current.