ZGS11-Z Integrated American-style Pad-Mounted Substation

The complete unit of the ZGS11-12 series integrated American-style pad-mounted substation features compact size, easy installation and maintenance, low noise, low losses, anti-theft design, full protection, and strong overload capacity. It is suitable for various locations such as new residential areas, green belts, parks, station hotels, construction sites, airports, and more.

  • Fully Custom
  • Expedited Production Processing

This product complies with the following standards

  • GB 17467 "High-voltage/Low-voltage Prefabricated Substations
  • DL/T 537 "Guide for Selection of High-voltage/Low-voltage Prefabricated Compact Substations"

Dimensions

Model Number and Designation Explanation ZGS  ¨- 12/0.4 (¨) / ¨  ¨ ① ②  ③   ④ ⑤ ⑥
Prefabricated Substation (American Style) HV Switchgear Main Switch Type: F-Load Break Switch; F·R-Load Break Switch + Fuse
Design Serial Number HV Switchgear Operating Mechanism Type: T-Spring Operating Mechanism; S-Manual Operating Mechanism
 Rated Voltage (kV) Transformer Rated Capacity (kVA)
    Technical Parameters
No. Parameter Unit Value
1 Rated Voltage KV 10/4(HV/LV)
2 Maximum Operating Voltage KV 12(HV Side)
3 Rated Frequency HZ 50
4 Rated Capacity KVA 50-1600
5 Power Frequency Withstand Voltage (1 min) KV 35
6 Lightning Impulse Withstand Voltage KV 75
7 Cooling Method   Oil-Immersed Self-Cooled
8 HV Backup Fuse Breaking Current KA 50
9 Insertable Fuse Breaking Current KA 25
10 Ambient Temperature °C -35~+40
11 Allowed Winding Temperature Rise °C 65
12 Off-Circuit Tap Changer   ±5%±2X2.5%
13 Sound Level db 50
14 Protection Degree   IP43
Installation Dimension Drawing